Nil
None
E
With feet and no rack mounting brackets
F
With flow switch
P
High-pressure pump mounted
Nil
Rc
N
NPT thread
A
Air-cooled
2
200 to 240 VAC HECR010
5
100 to 240 VAC HECR002, 004, 006, 008
002
200 W
004
400 W
006
510 W
008
800 W
010
1 kW
(UL Standards)
5A
Cooling capacity
Radiating method
Power supply
Option
Pipe thread
How to Order
Specifications
Model
HECR002-A HECR004-A HECR006-A HECR008-A HECR010-A
Cooling method Thermoelectric device (Thermo-module)
Radiating method Forced air cooling
Control method Cooling/Heating automatic shift PID control
Ambient temperature/humidity 10 to 35°C, 35 to 80% RH (No condensation)
Circulating fluid system
Circulating fluid Tap water, Ethylene glycol 20%
Set temperature range 10.0 to 60.0°C (No condensation)
Cooling capacity
200 W (Tap water)
∗
1
400 W (Tap water)
∗
1
510 W (Tap water)
∗
1
800 W (Tap water)
∗
2
1 kW (Tap water)
∗
2
Heating capacity
600 W (Tap water)
∗
1
1 kW (Tap water)
∗
1
1.2 kW (Tap water)
∗
1
1.4 kW (Tap water)
∗
2
2 kW (Tap water)
∗
2
Temperature stability
∗
3
±0.01 to 0.03°C
Pump capacity Refer to the performance charts. (Pages 10 and 11)
Tank capacity Approx. 1.3 L
Port size Rc1/4 Rc3/8
Fluid contact material
Stainless steel, EPDM, NBR, Ceramics,
PPE, Carbon, PP, PE, PPS (High pressure)
Stainless steel, EPDM, NBR, Ceramics, PPE, PPS, Carbon, PP, PE, Nylon,
POM (HECR008, 010), PVC (High pressure)
Electrical system
Power supply Single-phase 100 to 240 VAC ±10%, 50/60 Hz
Single-phase 200 to 240
VAC ±10%, 50/60 Hz
Overcurrent protector 10 A 14 A
Current consumption
5 A (100 V) to 2.5 A (240 V)
9 A (100 V) to 4 A (240 V)
10 A (100 V) to 4 A (240 V)
8 A (200 V)
Power consumption 440 W
∗
1
850 W
∗
1
900 W
∗
2
1500 W
∗
2
Alarm Refer to “Alarm.” (Page 20)
Communications RS-232C/RS-485
Weight Approx. 14 kg Approx. 18 kg Approx. 21 kg Approx. 31 kg Approx. 33 kg
Accessories
Power supply connector, Operation Manual
Power supply cable should be ordered as an option (sold separately, page 22) or prepared by the user.
Safety standards CE marking, UL (NRTL) standards
∗1 Conditions: Set temperature 25°C, Ambient temperature 25°C, Circulating flow rate 3 L/min
∗2 Conditions: Set temperature 25°C, Ambient temperature 25°C, Circulating flow rate 4 L/min
∗3 The indicated values are with a stable load without turbulence in the operating conditions. It may be out of this range in some other operating conditions.
¡ When multiple options are combined, indicate
symbols in alphabetical order.
HECR 002
Thermo-con/
Rack Mount Type
HECR Series
Air-cooled
7