RoHS
Power supply
20
3-phase 200 VAC (50 Hz)
3-phase 200 to 230 VAC (60 Hz)
40
3-phase 380 to 415 VAC (50/60 Hz)
Option
Nil
None
B
Note)
With earth leakage breaker
J
With automatic fluid fill function
M
Applicable to deionized water piping
OWhen multiple options are combined,
indicate symbols in alphabetical order.
Note) 200 V type only.
400 V type is provided with an earth leakage breaker as standard.
A090HRS
(Only 400 VAC type)
20
How to Order
Specifications
Model HRS090-Al-20-l HRS090-Al-40-l
Cooling method Air-cooled refrigeration
Refrigerant R410A (HFC)
Refrigerant charge kg 1.15
Control method PID control
Ambient temperature
∗
1
°C
5 to 45
Circulating fluid system
Circulating fluid
∗
2
Tap water, 15% ethylene glycol aqueous solution, Deionized water
Set temperature range
∗
1
°C
5 to 35
Cooling capacity 50/60 Hz
∗
3
kW 8.0/9.0
Heating capacity 50/60 Hz
∗
4
kW 1.7/2.2
Temperature stability
∗
5
°C ±0.5
Pump
capacity
Rated flow 50/60 Hz (Outlet)
∗
6
L/min 29/45
Maximum flow rate 50/60 Hz L/min 55/68
Maximum pump head m 50
Minimum operating flow rate 50/60 Hz
∗
7
L/min 29/45
Tank capacity L 18
Circulating fluid outlet, circulating fluid return port Rc1 (Symbol F: G1, Symbol N: NPT1)
Tank drain port Rc1/4 (Symbol F: G1/4, Symbol N: NPT1/4)
Fluid contact material
Stainless steel, Copper (Heat exchanger brazing), Brass, Bronze, PTFE,
FKM, EPDM, PVC, NBR, POM, PE, PP, Carbon, Ceramic
Electrical system
Power supply
3-phase 200 VAC (50 Hz), 3-phase 200 to 230 VAC (60 Hz)
Allowable voltage range ±10% (No continuous voltage fluctuation)
3-phase 380 to 415 VAC (50/60 Hz)
Allowable voltage range ±10% (No continuous voltage fluctuation)
Applicable earth leakage
breaker (Standard)
Rated current A 30 20
Sensitivity of leak current
mA 30
Rated operating current 50/60 Hz
∗
5
A 16/18 8.4/9.1
Rated power consumption 50/60 Hz
∗
5
kW (kVA) 4.3/5.4 (5.5/6.0) 4.4/5.6 (5.8/6.3)
Noise level (Front 1 m/Height 1 m)
∗
5
dB (A) 73 75
Accessories
Alarm code list stickers 2 pcs. (English 1 pc./Japanese 1 pc.),
Operation Manual (for installation/operation) 2 pcs. (English 1 pc./Japanese 1 pc.),
Y-strainer (40 meshes) 25A, Barrel nipple 25A,
Anchor bolt fixing brackets 2 pcs. (including four M10 bolts)
∗
8
Weight (dry state) kg Approx. 136
∗1 Use a 15% ethylene glycol aqueous solution if operating in a place where the ambient temperature and/or circulating fluid temperature is 10°C or less.
∗2 Use fluid in condition below as the circulating fluid.
Tap water: Standard of The Japan Refrigeration And Air Conditioning Industry Association (JRA GL-02-1994)
15% ethylene glycol aqueous solution: diluted by tap water in condition above without any additives such as antiseptics.
Deionized water: Electric conductivity 1 mS/cm or higher (Electric resistivity 1 MW·cm or lower)
∗3 q Ambient temperature: 32°C, w Circulating fluid: Tap water, e Circulating fluid temperature: 20°C, r Circulating fluid flow rate: Rated flow, t Power supply: 200/400
VA C
∗4 q Ambient temperature: 32°C, w Circulating fluid: Tap water, e Circulating fluid flow rate: Rated flow, r Power supply: 200/400 VAC
∗5 q Ambient temperature: 32°C, w Circulating fluid: Tap water, e Circulating fluid temperature: 20°C, r Load: Same as the cooling capacity, t Circulating fluid flow
rate: Rated flow, y Power supply: 200/400 VAC, u Piping length: Shortest
∗6 When circulating fluid outlet port pressure = 0.5 MPa.
∗7
Fluid flow rate to maintain the cooling capacity and to keep the circulating fluid discharge pressure to 0.5 MPa or less. If the actual flow rate is lower than this, install a bypass piping.
∗8
The anchor bolt fixing brackets (including four M10 bolts) are used for fixing to wooden skids when packaging the thermo-chiller. No anchor bolt is included.
Pipe thread type
Nil
Rc
F
G (with Rc-G conversion fitting)
N
NPT (with Rc-NPT conversion fitting)
Cooling method
A
Air-cooled refrigeration
Cooling capacity
090
9 kW
Thermo-chiller
Air-cooled 200 V/400 V Type
Standard Type
HRS090 Series
76
A